| under-floor
air-conditioning system Introduction
Under-floor air-conditioning systems
have been installed in other parts of the world for nearly 20 years. In Singapore,
one form of under-floor air-conditioning systems is commonly found in the computer
room air-conditioning where the cool air is supplied from the floor.
Concept Of Underfloor Air-Conditioning System In
general, under-floor air-conditioning system (UAS) uses the same air-conditioning
equipment, namely, chillers, pumps, cooling towers and AHUs as in conventional
air-conditioning system. The main difference between the two is the manner that
air is being distributed. Conventional system supplies air from the ceiling level
while UAS supplies air from floor level and returns to the air-handling unit from
the ceiling.

UAS
by virtue of its design has the advantage of moving air in the same direction
as the thermal lift in the room. Heat generated from the occupied zone normally
moves upwards. This upward movement helps the UAS in removing heat from the occupied
zone. It is important to note that the conventional system supplies air from the
top and continuously fights against the thermal lift. The cool supply air mixes
with the rising heat from the occupied zone and it will require a colder supply
air to provide the same space condition.
Temperature Distribution In Occupied Zone The
supply air temperature in the UAS should be around 17-18 °C. This is to ensure
that the room temperature near the floor level is 0.5 to 1° C lower than that
at a level of 1.8 m above the floor. This means that with the room temperature
in the occupied zone around 22-24 °C, the return air temperature could be
around 25-28 °C depending on the specific room cooling load.
Normally,
the supply air is mixed with about 10 to 20% "fresh" air from outside
before entering the cooling coil. In Singapore's context, it is advisable to have
this outside air pre-cooled prior to being mixed with the return air. This is
to ensure that both the temperature and humidity of the air mixture are better
controlled. Furthermore, since a supply air temperature of 17-18 °C is required,
the air-handling unit should be equipped with a modulating face and by-pass damper
so that the desired supply temperature can easily be achieved by mixing the conditioned
off-coil air with unconditioned re-circulated air.
Reduced Energy Consumption Energy
consumption in a UAS is lower than the conventional overhead system in many ways:
(a) For commercial office space, CP13:1999 prescribes
that the minimum outside air quantity shall be 2.3 m3/h per m2 floor area. This
ventilation requirement is based on a theoretical ventilation effectiveness, Ev
= 1.0, However, in conventional system where both the supply air and return air
grilles are fixed on the suspended ceiling, it is common for the supply air to
be short-circuiting into return air or disruption of supply air by partition walls
before reaching the occupied zone. As a result, Ev is always less than 1.0. In
fact various studies show that an Ev of as low as 0.65 for conventional overhead
system is normal. With Ev = 0.65, actual outside air quantity to be introduced
into the air-conditioned space would need to be increased to 3.5 m3/h floor area.
This represents an increase in equipment cooling capacity of 12.5 Watt per m2
or 3.54 RT for a 1,000 m2 office space which is nearly 10% of the total cooling
load. In the case of UAS, 100% of the outside air passes directly through the
occupied zone towards the ceiling return system. Hence, Ev of 1.0 is achievable
and the minimum prescriptive outside air quantity is adequate.
(b) UAS with minimal ductwork uses lower fan pressure. To maintain a plenum pressure
of 30 to 40 Pa, the typical UAS total system pressure is only 200 to 300 Pa. This
is significantly lower when compared with a system pressure of over 600 pa for
a conventional overhead system. From the Fan Law, where fan electrical power is
proportional to the cube of the square root of system pressure, the energy saving
is obvious for the UAS. This works out to be 3 to 5 times more fan energy in the
case of conventional system. (c) UAS
supplies air in the same direction as the thermal lift (rising heat) and thus
consumes less energy (fan) to cool the building. Furthermore the unoccupied zone
is not cooled to comfort temperature unlike the conventional system. This stratified
zone can easily constitute 40% of room volume. (d)
Higher supply air temperature of 18°C for UAS as compared with 13°C for
the conventional system requires lower refrigeration energy (compressor). Chiller
savings result from using higher chiller leaving water temperatures due to the
higher supply air temperatures. However, these cooling energy savings can be substantially
reduced or eliminated because of the need for moisture control in humid climates
such as Singapore will require pre-cooling of fresh air.
Capital Cost With
the drastic reduction in ductworks, the capital cost of a UAS shall theoretically
be lower. Any ductwork required will be minimal and is of low pressure type. However,
there is possible increase in cost if several smaller AHUs are used in lieu of
a big one. The twist floor outlets are more costly that ceiling grilles. Additional
insulation will be required for the concrete floor. Hence, the capital cost for
air-conditioning installation will be only marginally lower.
There
is possible saving in the installation of the second tier of automatic sprinkler
system inside the false ceiling space if its height can be reduced to less than
800mm. However, if the height of the under-floor space is more than 300mm, we
have to install a smoke detection system in the under-floor space thereby increasing
the cost. Hence, the capital cost for fire protection/detection installation may
also be only marginally lower.
| Conventional
System | Under-floor
System | Increase(+)/
Reduction(-) | | Clear
room height | 2.7m |
2.7m | 0% |
| Height of under-floor space |
0.2m | 0.4m |
+100% |
| Height of ceiling space(assuming a beam
depth of 0.6m) | 1.4m |
0.8m | -43% |
| Total floor to floor height |
4.3m | 3.9m |
-9.3% |
Under-floor air-conditioning can offer
great saving in overall cost but it requires a coordinated team approach from
the outset of the project so as to achieve the optimal result. From an article
on this subject in the January 2002 issue of Journal of the Chartered Institution
of Building Services Engineers, it mentioned Swedish National Pension Fund has
reported savings in overall cost of in the region of 5% to 7% of total construction
cost. More
Flexibility For Changes The
UAS offers full flexibility in changes to office layout. Changes to an under-floor
air-conditioning system require few if any costs for rewiring and re-balancing.
The pressurised plenum is self-balancing. The UAS floor outlets can be re-located
quite easily to suit any new workstation layout, thus facilitating re-organization
of office layouts as well as savings in renovation/refurbishing costs and time.
With conventional system, space air circulation is often severely hindered by
the siting of partitions and workstations. This will reduce subsequent renovation
cost.
Conclusion
Despite the advantages of under-floor
systems, there are barriers to widespread adoption of UAS technology. There is
a perceived higher risk to designers and building owners due to a lack of objective
information and standardised design guidelines, perceived higher costs, problems
with standards and codes, and a lack of documented case studies with whole-building
performance and cost-savings data.
|